Info
Suitable for the following facilities: –
- ITC-BT 9 Underground power networks for outdoor lighting installations
- ITC-BT 20 Indoor or reception installations
- ITC-BT 26 Indoor installations in housing
- ITC-BT 27 Indoor installations in housing. Premises containing a bath or shower
- ITC-BT 30 Installations in premises with special characteristics
- ITC-BT 41 Electrical installations in caravans and caravan parks
Application
H05V-K CPR cables complies with the construction product classification according to the CPR Regulation 305/2011 and the standard EN 50575 standard, which are indicated for fixed installations, electrical control panels, control and signalling circuits.
Regulations | General Properties
- Non-flame propagating according to UNE-EN 60332-1-2, EN 60332-1-2 and IEC 60332-1-2
Construction
- Conductor: Flexible electrolytic bare copper (Class 5) according to UNE-EN 60228, EN 60228 and IEC 60228
- Insulation: PVC type TI-1 according to UNE-EN 50363-3 and EN 50363-3
- Cover color: according to UNE-EN 50525-1
Specifications
- Nominal voltage 300/500 V
- Test voltage 2.000 V C.A.
- Maximum temperature 70 °C (160°C Short circuit temperature)
- Minimum bending radiu 5 x
- Outer diameter (fixed inst.)
- Operating temperature -25 °C a +70 °C