Info
- With high mechanical protection and electromagnetic shielding
- According to ITC-BT-029 of the Low Voltage Electro-technical Regulation for electrical installations at premises with risk of fire and explosion.
Application
Specially designed for temperature measurement equipment For the interconnection of thermocouples, for example in petrochemical plants
Regulations | General Properties
- Flame retardant according to EN60332-1-2 / IEC60331-1-1
- Fire retardant according to EN50266-2-4 / IEC60332-3-24
- Resistant to hydrocarbons and mineral oils according to UIC-895OR
- Good resistance to chemicals
- Good resistance to water jets
- Excellent mechanical strength
- Good electromagnetic shielding
- Suitable for indoors and outdoors
Construction
- Conductor (see chart on page 20)
- PVC insulation
- Conductor identification: blue and numbered black or white and numbered black
- Stranding arranged in pairs, with at least 15-20 turns per meter
- All pairs wired as a whole set in concentric crowns
- Pair shield made of polyester tape + tinned copper drain wire + aluminum/polyester tape
- 100% shield coverage, with a minimum overlap of 25%
- General shield made of polyester tape + tinned copper drain wire + aluminum/polyester tape
- Bedding / PVC inner sheath, resistant to hydrocarbons and mineral oils
- Crown-shaped armor of galvanized steel wires
- Minimum armor coverage of 90%
- Outer PVC sheath, resistant to hydrocarbons and mineral oils
- Sheath colour (see chart)
Specifications
- Minimum bending radius: 12 x outer diameter
- Temperature range * –40ºC to +105ºC in fixed installation
- Insulation impedance > 1M? x km
- Rated voltage 500V
- Test voltage 1,500V C.A. for 5 min.
- Temperature range * –25ºC to +90ºC in fixed installation