Info
- Profibus PA for fixed installation.
Application
Armoured profibus PA cable for fixed installation. Suitable for all kinds of industrial plants, in areas where mechanical protection is required or where the cable is subject to significant tensile stress.
Regulations | General Properties
- Flame retardant IEC 60332-1-2 y UL 1685 (CSA FT 4),
- Resistant to oils according to UL 13 Sec. 40 (60 °C),
- Resistant to ultraviolet rays according to UL 2556 Sec. 4.2.8.5,
- UL-File E119100 Vol. 1 Sec.16 Pág 6,
- UL-File E116441 Vol. 1 Sec. 6 Páge 6,
- UL-Style 21694
Construction
- Copper conductor (AWG18)
- Polyethylene foam insulation
- Red and green conductor identification
- Aluminium screen + tinned copper braid
- Internal PVC covering
- Galvanised steel wire armour
- External PVC covering
Specifications
- Operating voltage: 100 V
- Insulation resistance: ? 10 MOhm*Km
- Minimum operating temperature: -20 °C
- Maximum operating temperature: 80 °C
- Impedance: 100 ± 20 Ohm
- Loop resistance: < 44 Ohm/km
- Capability: 50 nF/km
- Attenuation: (39kHz) <3 db/km