Info
- According to ITC-BT-029 of the Low Voltage Electro-technical Regulation for electrical installations at premises with risk of fire and explosion.
Application
Shielded and armored instrumentation and control cable also suitable for motor power supply. Suitable for all types of industrial plants such as petrochemical stations, power plants, combined cycle thermal power plants, solar thermal energy plants, biodiesel production plants, etc.
Regulations | General Properties
- According to construction standards IEC60502
- Flame retardant according to EN60332-1-2 / IEC60331-1-1
- Fire retardant according to EN50266-2-4 / IEC60332-3-24
- Resistant to hydrocarbons and mineral oils according to UIC-895OR
- Good resistance to chemicals
- Good resistance to water impacts
- Excellent mechanical strength
- Suitable for indoors and outdoors
Construction
- Bare electrolytic copper, Class 5, flexible according to UNE 60228
- Insulation made of cross-linked polyethylene (XLPE)
- Conductor identification according to HD308 or EN50334
- Shield (only up to 2.5mm² section) made of polyester tape + tinned copper drain wire + aluminum/polyester tape
- 100% shield coverage, with a minimum overlap of 25%
- Shield (from 4 mm² section) made of bare copper wires braid
- PVC bedding / inner sheath, resistant to hydrocarbons and mineral oils
- Armor of galvanized steel wires, cross-wound of copper tape if necessary
- Minimum armor coverage of 90%
- PVC outer sheath, resistant to hydrocarbons and mineral oils
- Black colour
Specifications
- Rated voltage 0.6/1kV
- Test voltage 3,500V C.A. for 5 min.
- Temperature range –25ºC to 70ºC in fixed installation
- Maximum conductor temperature 90ºC (250ºC in case of short-circuit)
- Electrical resistance according to UNE 60228
- Maximum allowable intensity according to HD516
- Minimum bending radius: 10 x Outer diameter