Info
- Medium voltage in copper, insulation in xlpe
Application
Power distribution cable for use in indoors and outdoors Installation in conduit and directly buried
Regulations | General Properties
- IEC60502-2 (Design)
- IEC60332-1 / EN60332-1 (flame retardant)
Construction
- Circular conductor with copper compacted round thread, Class 2 according to IEC60228 / EN60228
- Semi-conductive internal shield extruded on the conductor
- Insulation made of polyethylene (XLPE) cross-linked in dry nitrogen atmosphere
- External semi-conductive extruded shield
- Crown-shaped metallic shield made of copper wires and cross-wound of copper tape on each conductor to avoid electromagnetic interferences from outside and those induced by the cable itself.
- Total shield section 16mm2 or 25mm2
- Tape-shaped separator
- PVC outer sheath type ST2
- Red colour
Specifications
- Rated voltage ?6/10 kV
- Test voltage ?24 kV
- Rated voltage ?8.7/15 kV
- Test voltage ?32 kV
- Rated voltage ?12/20 kV
- Test voltage ?42 kV
- Rated voltage ?18/30 kV
- Test voltage ?63 kV
- Conductor maximum rated temperature 90º C
- Conductor maximum temperature in case of short-circuit 250º C / k = 152
- Minimum rated temperature –10º C (Below 0° C special precautions must be taken)
- Bending radius in fixed installation 10 x outer diameter
- Bending radius during installation 15 x outer diameter