Info
- Insulation in high modulus ethylene propylene with excellent mechanical characteristics
Application
Power distribution cable for use in indoors and outdoors Installation in conduit and directly buried
Regulations | General Properties
- IEC60502-2 (Design)
- IEC60332-1 / EN60332-1 (flame retardant)
- IEC60332-3 / EN50266 (fire retardant
- IEC60754-1 / EN50267-2-1 (halogen free)
- IEC60754-2 / EN50267-2-2 (Low emission of corrosive smoke)
- IEC61034 / EN50268 (Low emission of opaque smoke)
Construction
- Circular conductor with copper compacted round thread, Class 2 according to IEC60228 / EN60228
- Semi-conductive internal shield extruded on the conductor
- Insulation made of high modulus rubber (HEPR), cross-linked in dry nitrogen atmosphere
- External semi-conductive extruded shield made of conductive material separable in cold
- Crown-shaped metallic shield made of copper wires and cross-wound of copper tape on each conductor to avoid electromagnetic interferences from outside and those induced by the cable itself.
- Total shield section 16mm2 or 25mm2
- Tape-shaped separator
- Polyolefin halogen free outer sheath
- Red colour
Specifications
- Rated voltage?12/20 kV
- Test voltage?42 kV
- Rated voltage?18/30 kV
- Test voltage?63 kV
- Conductor maximum rated temperature?90º C
- Conductor maximum temperature in case of short-circuit?250º C / k = 152
- Minimum rated temperature?–15º C (Below –5° C special precautions must be taken)
- Bending radius in fixed installation 10 x outer diameter
- Bending radius during installation 15 x outer diameter